Abstract
This paper investigates the performance of various adsorbent/refrigerant working pairs in a cascaded adsorption system using Simulink/Matlab software. The cascaded system consists of two pairs of adsorber beds, condenser, evaporator and an integrated condenser/evaporator heat exchanger, forming upper and bottoming cycles. Four combinations of working pairs were investigated: ATO-Ethanol + Maxsorb/R507A, Maxorb/R134a + Maxorb/Propane and ATO/Ethanol + Maxorb/Propane and Maxorb/R134a + Maxsorb/R507A. The latter case was used for validation and as a reference point for assessing the performance of the investigated working pairs in term of COP and cooling capacity. Results showed that the Maxorb/R134a + Maxorb/Propane combination gives a higher enhancement compared to reference one with up to 30.0% and 30.1% for the COP and cooling capacity, respectively. ATO/Ethanol + Maxorb/Propane combination is the cheapest but with lower performance.
Original language | English |
---|---|
Pages (from-to) | 1496-1501 |
Number of pages | 6 |
Journal | Energy Procedia |
Volume | 75 |
DOIs | |
Publication status | Published - 1 Jan 2015 |
Event | 7th International Conference on Applied Energy, ICAE 2015 - Abu Dhabi, United Arab Emirates Duration: 28 Mar 2015 → 31 Mar 2015 |
Keywords
- Adsorption
- Cascading
- Freezing
- Simulink
- Working Pairs
ASJC Scopus subject areas
- General Energy